GX-1100
Local display & transmitter type combustible (IR sensor), toxic, oxygen gas detector
FEATURES
FND digital display
4 to 20mA transmission
Wide variety of the sensor
Excellent reliability
SPECIFICATION
| Model | GX-1100 (IR) | GX-1100 (ELC) | GX-1100 (O2) |
| Measuring gas | Combustible gas | Toxic gas | Oxygen gas |
| Measuring range | 0 to 100% LEL | ppm | 0~25Vol. % |
| Detection principle | Infrared | Electro chemical | Galvanic cell |
| Display | 4 digit FND | 4 digit FND or LCD | |
| Sampling | Diffusion | ||
| Power | 18 to 30V DC | ||
| Power consumption | 2.4W (100mA) | 1.7W (70mA) or 0.5W (20mA) |
2.4W (100mA) or 0.5W (20mA) |
| Output signal | 4 to 20mA DC | ||
| Load impedance | 600Ω | 600 or 250Ω | |
| Local calibration | Yes | ||
| Explosion proof | Ex d IIC T6 IP65 | ||
| Detector housing | Aluminum diecasting | ||
| Sensor housing | SUS 316 | ||
| Dimension | 132(W)×161.65(H)×95~98(D) | ||
| Cable | CVVS 1.5SQ, 3wire | CVVS 1.5SQ, 3wire or 4wire | |
| Response time | Less than 15 seconds at T90 |
Depends on the sensors |
Less than 5 seconds at 5vol% |
| Zero / span drift | ±3% | ||
| Accuracy | ±3% | ||
| Expected life | 60 month | 18 to 24 month | |
| Operating temp. | -20℃ to 50℃ | ||
| Alarm set point (model name+C) | Two independent (H, HH) | Two independent (H, HH) | |
| Alarm set valve (model name+C) | 0 to F.S. programmable | ||
| Alarm output (model name+C) | 3 X SPDT N.O or N.C (H, HH, fail) | ||
ACCESSORIES




Calibration Kits
Adaptor & Splash guard
Weather proof cover&u-bolt
WBH-100 (Horn&Beacon)




Magnetic bar